390 Configuration
How to configure SDI with time monitoring
Example:
The figure below shows an example of an SDI positive function with time
monitoring set-up:
• Version 1 of SDI functions activated (
Version 1
)
• SDI positive function activated (
Enabled
)
• time monitored ramp (
SDI activation monitoring method
Time
)
• deceleration ramp according to drive parameters (always with time monitoring)
• SDI activation delay 2000 ms (
=
2000 ms
)
• SDI tolerance into the forbidden direction 2 degrees
2 deg
)
• automatic acknowledgement (
Automatic
)
• redundant activation button connected to input
DI X113:2 & X114:2
)
• single output connected (
=
DO X114:7
).
= DI X113:2 &
X114:2
= None
= DO X114:7
= None
= Time
= Automatic
= 2000 ms
SDI positive
Time
Speed
Inputs
Outputs
SDI activated
SDI monitoring started
= Version 1
= 2 deg
(not shown in the
figure)
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...