440 Parameters
Est switch not active
load
With some restrictions, the FSO module
sends a warning to the drive and starts to
use an estimated value of the motor speed
until the failure is fixed.
For more information, see section
on page
Note
: Do not use this selection in
applications with active load. See section
on page
.
Note:
Safe speed estimate cannot be used
with a DCS880 drive.
S_ENCGEN.
14
Enc speed cross
comp tolerance
Sets the encoder speed cross comparison
tolerance. This defines how much the motor
shaft speed can change within 1 ms. If the
tolerance is exceeded, the FSO module
reaction depends on the
selection.
Note:
This parameter is used for the
encoder diagnostic. It defines how large the
difference between the speed information
from channel A and B of the encoder can be.
If the difference between these two values is
greater than the value set to this parameter,
FSO will safely stop the system (STO).
The suitable value depends on the
configuration (motor / load). Typically this
value is set to 2-10 rpm; a very low value will
cause an encoder fault (A7D8) whereas too
high a value will prevent encoder diagnostic
related to this parameter.
0.0 rpm
0.0 …500.0 rpm
Speed
S_ENCGEN.
41
Gear numerator
encoder 1
Sets the rotation direction for the safety
encoder. With this parameter, you can
change the rotation direction of the motor.
1
Positive direction.
-1
Negative direction.
41
Enc module
settings
Parameters for the safety encoder interface
module
91.11 Module 1 type
Sets the type of the safety encoder interface
module 1.
None
The safety encoder interface module is not
in use.
FSE-31
The type of the safety encoder interface
module is FSE-31.
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...