Parameters 441
91.12 Module 1 location
Sets the slot in which the safety encoder
interface module is located.
1
Slot 1 on the drive control board.
2
Slot 2 on the drive control board.
3
Slot 3 on the drive control board.
41
Encoder 1 configuration
Parameters for safety encoder 1
92.01 Encoder 1 type
Activates the communication with the safety
encoder interface module 1 and sets the
type for the safety encoder.
HTL1
Communication active.
Module type: FSE-31.
Input: HTL encoder input (X31).
92.02 Encoder 1 source
Sets the safety encoder interface module
that the safety encoder 1 is connected to.
Module 1
The safety encoder 1 is connected to
interface module 1.
92.10 Pulses/revolution
Sets the number of HTL pulses per
revolution for safety encoder 1.
0
0…65535
Pulse rate of the encoder used
92.17 Accepted pulse freq
of encoder 1
Sets the maximum pulse frequency of
encoder 1 (see
on page
).
If the measured pulse frequency of the
safety encoder is higher than the value set
here, the FSO module reaction depends on
the
selection.
0.0 kHz
0…300 kHz
Frequency
41
SAFEIO
Parameters for FSO inputs and outputs
SAFEIO.11 M/F mode for
cascade
Sets the master/follower mode of the FSO
module for both cascade connections A and
B separately.
A = follower,
B = follower
The module is a follower on cascade
connection A and a follower on cascade
connection B.
A = master,
B = follower
The module is the master on cascade
connection A and a follower on cascade
connection B.
A = follower,
B = master
The module is a follower on cascade
connection A and the master on cascade
connection B.
A = master,
B = master
The module is the master on cascade
connection A and the master on cascade
connection B.
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...