Configuration 319
In addition, you must install the FB module to the drive and set up the safety
communication network between the modules as described in chapter
.
Example
:
• PROFIsafe communication activated
Version 1
and
=
PROFIsafe
)
• Speed scaling: 1500 rpm
SBUSGEN. 06 Safety fieldbus speed scaling
=
1500 rpm
)
• When an encoder is used: Position scaling: 1000
SBUSGEN. 07 Safety fieldbus position scaling
1000
)
• the FSO module generates a fault message if the module is passivated due to
safety fieldbus problems
(
Fault
)
• the FB module is connected to option slot 1
FBA A
and
1
)
• PROFIsafe profile ABB_PS1 in use
PROFIsafe. 12 PROFIsafe telegram type
=
0x221
)
• IP address of the FB module: 1
PROFIsafe.11 PROFIsafe F_Dest_Add
= 1
)
Configuring I/O
How to configure I/O
To configure the I/O, set the FSO parameters shown in the figure below to
appropriate values using the Drive composer pro PC tool. See parameter group
=
PROFIsafe
= FBA A
=
1
=
0x221
= Version 1
= 1500 rpm
= 1
FB
module
Safety PLC
FSO
ACS880 drive
= Fault
= 1000
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...