Safety functions 119
Step Description
1
The SSE request is received (for example, from the I/O). The FSO starts a counter for
time A. SSE active indication
) goes on.
2
After time C has elapsed, the drive starts to ramp down the motor speed. SAR0
parameter
defines the deceleration ramp.
3
The motor speed reaches the zero speed limit (B), the FSO activates the drive STO
function and STO active indication parameter
) goes on. The SSE
completed indication goes on and the acknowledgement becomes allowed as soon as
the SSE request has been removed (step 4).
Note
: If the SBC is configured in the STO function (see section
page
), also the SBC is activated (not shown in the figure).
• If the
(parameter
) is negative, the SBC is activated here and
the drive STO after this delay.
• If the
is positive or zero, the SBC and drive STO functions are
activated at the same time.
Note
: You can define an extra delay (parameter
) before the FSO activates the
drive STO (and SBC, if used) (not shown in the figure).
3b
If the drive has not ramped down fast enough when time A has elapsed, the FSO
activates the STO function. See section
on page
for more
information on how to configure the STO function.
4
The SSE request is removed.
5
After the acknowledgement, the STO and SSE functions are deactivated. The
indications
(
) go off.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...