224 PROFIsafe
PROFIsafe response time
The safety function response time (SFRT) is the time within which the safety system
must react after an error has occurred in the system.
SFRT is also the maximum time within which the safety system must respond to a
change in the input signals.
According to
PROFIsafe System Description, Version November 2010,
SFRT for
PROFIsafe devices can be
defined as:
SFRT = TWCDT + Longest
∆
T_WD
where
• TWCDT (total worst-case delay time) is the maximum time for input signal transfer
in the safety system until the output reaction under worst-case conditions (all
components require the maximum time)
• Longest
∆
T_WD is the longest time difference between the watchdog time for a
given entity and the worst-case delay time.
In safety systems, to define SFRT you must take into account a potential single fault
in one of the components during the signal transfer. It is enough to consider a single
fault only (see
PROFIsafe System Description, Version November 2010)
.
The worst-case delay time (WCDT) and watchdog (WD) values for the FSO and
FENA modules are listed in the table below.
The documentation of the safety PLC defines how you can calculate the processing
time and transmission time of the PROFIsafe connection.
For example,
AC500-S Safety User Manual
(3ADR025091M0207 [English]) proposes
that SFRT is calculated using the following formula:
SFRT = Devi 0.5 x F_WD F_H 0.5 x F_WD_Time2
+ Devi Longest
∆
T_WD
Device
WCDT
Device WD
FSO
50 ms
50 ms
FPNO-21
3 ms
-
FENA-21
3 ms
-
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...