216 PROFIsafe
Operational
PROFIsafe communication is up and running. The safety application is
running without any detected errors.
PROFIsafe Status Byte bits in the F-Host for the FSO module:
• OA_Req_S = 0
• FV_activated_S = 0
• Device_Fault = 0
ABB_PS1 or ABB_PS2 profile bits in the F-Host for the FSO module:
• FSO_mode.1 = 0
• FSO_mode.0 = 1
• SF_end_ack_req_local = 0
• SF_end_ack_req = 0
• FSO_state = 0
State
Description