![ABB FSO-21 User Manual Download Page 473](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728473.webp)
Verification and validation 473
Validation of the SS1 function
1. Make sure that the input for the SS1 function is configured according to the wiring
diagram.
2. Make sure that the SS1 function, and SAR1 setting or time monitoring limit is
configured correctly according to your design. For a configuration example, see
chapter
How to configure SS1 with time monitoring (SS1-t)
, or
to configure SS1 with ramp monitoring (SS1-r)
on page
. Check these
settings:
Activation:
•
•
.
•
Note:
activation can also come from the PROFIsafe
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
•
= Version 1
•
SS1-r ramp zero speed delay for STO
(if used)
•
•
•
drive parameter
23.23 emergency stop time
, if
= 0 ms
•
if with safe speed estimation:
•
•
a) If ramp monitoring is in use:
-
= SS1-r
OR
b) If time monitoring is in use:
-
= SS1-t
Indication:
•
•
•
.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...