Parameters 419
0…3,600,000 ms
Time
SSE.16 SSE ramp zero
speed delay for STO
Sets an extra delay time for the drive STO
(and SBC, if used) activation at the zero
speed limit in the SSE with emergency ramp
function.
With this parameter, the FSO module delays
the STO activation so that the drive is able to
reach the shaft zero speed before the FSO
module activates the drive STO function.
The delay counter starts when the motor
speed reaches the zero speed limit
(parameter
After this delay has elapsed, the FSO
module activates the drive STO function.
You can use this parameter when the motor
rotates a heavy load (high inertia).
Note:
The FSO module activates the drive
STO immediately if the drive stops
modulating before this delay has passed
(that is, the motor actual speed reaches
0 rpm).
30,000 ms
0…30,000 ms
Time
SSE.21 SSE output
Sets the digital output that indicates the
activity of the SSE function. Active from the
SSE request until the function has been
acknowledged.
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7
Single output X113:7
DO X113:8
Single output X113:8
DO X113:9
Single output X113:9
DO X114:7
Single output X114:7
DO X114:8
Single output X114:8
DO X114:9
Single output X114:9
SSE.22 SSE completed
output
Sets the digital output that indicates the
completion of the SSE function. See the
diagrams in section
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...