PROFIsafe 259
20. Check the protection of the controller station:
•
In the hardware configuration, double-click the controller station (for example,
CPU 319F-3).
•
Select
Protection
tab.
•
Select
1: Access protect. for F CPU
.
•
Check
Can be bypassed with password
.
•
Enter the password twice to the edit boxes.
•
Check
CPU contains safety program.
21. Save, compile and download the hardware configuration to the PLC.
The PLC is now ready for communication with the FENA adapter module.