Configuration 375
How to configure SMS, version 2
Example:
The figure below shows an example of the SMS, version 2 set-up:
• SMS function version 2 activated (
Version 2
)
• SMS limit positive (
1750
)
• SMS limit negative (
=
-1150
)
• SMS trip limit positive 1800.0 rpm (
= 1800 rpm
)
• SMS trip limit negative -1200.0 rpm (
=
-1200 rpm
)
• SSE function configured as immediate STO
Immediate STO
).
• See also section
on page
Note
: If you also use an SLS function, the SMS positive and negative trip limits must
be more than the speed defined by the corresponding SLS positive trip limit and less
than the speed defined by the corresponding SLS negative trip limit, respectively.
Related safety functions
The FSO module activates the SSE function if the motor speed hits an SMS trip limit.
See section
on page
.
= 1800 rpm
= 1750 rpm
= -1150 rpm
= -1200 rpm
Version 2
Speed
Time
SSE activated
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...