230 PROFIsafe
Note
: When the FB module is installed to the drive for the first time, you must set the
value of parameter
51/54.02
to one of the PROFINET profiles (value
11
if a drop-
down list is unavailable) and reboot the FB module with parameter
51/54.27
. Only
after this, the rest of the parameters in group 51/54 get the correct texts and options.
If required, you must reconnect Drive composer pro to the drive to get the parameters
show up correctly (select
Refresh
from the
New
menu).
See the FB module user’s manual and the drive firmware manual for all necessary
parameter settings and detailed instructions on how to control the drive and motor
using the normal PROFINET cyclic communication.
Configuring the FSO module
Set the FSO module parameters as described in section
.
51/54.02
FBA A/B PAR2
(PROTOCOL/
PROFILE)
Selects one of the PNIO profiles.
11
PNIO ABB Pro
Profile PNIO ABB Pro is selected
51/54.03
FBA A/B PAR2
(COMMRATE)
Sets the Ethernet communication rate.
0
Auto
Ethernet communication rate is negotiated
automatically by the device.
51/54.04…13 IP
CONFIGURATI
ON
The user can set the IP configuration for the
network in these parameters or in the PLC
project.
Static IP
0
51/54.20
Telegram type
Shows the telegram type for the selected I/O
communication.
This parameter is read-only.
4
PPO4
PPO Type 4
51/54.21
Alarm disable
Enables/disables the sending of diagnostic
messages to the PROFINET network.
0
Enabled
Diagnostic messages are sent.
51/54.27
FBA A/B PAR
REFRESH
Validates any changed FB module configuration
settings and reboots the FB module taking all the
changes to the drive parameters in use. After
refreshing, the value reverts automatically to
Done (0).
Note
: This parameter cannot be changed while
the drive is running.
1
REFRESH
Refreshing.
Index
Name/Value
Description
Example
value
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...