Verification and validation 463
b) If you have configured FSE diagnostic failure reaction (
) to be
No STO
:
1. Cause an encoder failure by disconnecting the one encoder signal channel
wire from the FSE module.
2. Activate any safety function except POUS or SSM.
3. Make sure the FSO module goes into the Fail-safe state, FSO general fault
) and FSO safety encoder fault (
) are indicated in the event log,
the STO function of the drive is activated, and the drive trips for the encoder
failure.
Repeat steps 1…3 after step 13 with no safety functions active to make sure that
the system does not trip to encoder fault.
14. Make sure that there are no unwanted faults in the drive event log.
15. Reconnect the encoder signal channel.
16. Re-boot the FSO module to exit the Fail-safe mode.
17. Restart the drive and make sure that the motor runs normally.
If you have configured FSE diagnostic failure reaction (
) to be
Est
switch not active load
, follow the steps below to validate the safety encoder interface:
12. Make sure that you can run and stop the motor freely.
13. Start the drive to the motor speed typical for the application.
14. Cause an encoder failure by disconnecting the one encoder signal channel wire
from the FSE module.
15. Make sure that the correct warnings are generated: Encoder warning (
),
FSO general warning (
),
FSE Ch1 diag event (
and FSE Ch12 diag
event (
16. Activate a safety function (any other safety function except SDI, POUS or SSM).
17. Make sure that the system does not trip to encoder fault.
18. Reconnect the encoder signal channel.
All safety functions that are in use, must be validated both with the safe speed
estimation and with the safety encoder when
=
Est switch not active load
. Validation test about the transition from the
encoder to the safe speed estimate must be done by disconnecting the encoder
signal.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...