Fault tracing 497
Events
B790
FSO general
event
FSO module generated
an event other than a fault
or a warning.
See the tips in the Drive Composer
PC tool.
3)
B792
FSO undefined
event
FSO new version,
undefined event in the
drive event system.
Contact your local ABB
representative.
B793
FSE Ch1 diag
event
Encoder failure.
Check the encoder. In case of an
encoder event
A7E1 Encoder
warning
exists in the drive event log,
fix the encoder fault. FSO module
reset is also needed if the FSO
module is in the Fail safe mode.
B794
FSE Ch2 diag
event
Encoder failure.
Check the encoder. In case of an
encoder event
A7E1 Encoder
warning
exists in the drive event log,
fix the encoder fault. FSO module
reset is also needed if the FSO
module is in the Fail safe mode.
BA90 FSO stop
completed
FSO module has
completed the STO, SS1
or SSE function.
-
1)
BA91 FSO safe speed
limit
FSO module detected an
SLS or SMS speed trip
limit violation.
Check the separate code related to
SLS and SMS functions.
See section
for limit hits and special events
on
page
2) 3)
BA92 FSO out of eme
ramp
Motor speed was not
inside the ramp window
during the SSE function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
BA93 FSO ramp
coasted
Drive coasted the motor
to stop instead of using
the ramp.
Check that the FSO module zero
speed limit for the deceleration ramp
is not excessive (
or
).
2)
BA94 FSO out of safe
ramp
Motor speed was not
inside the ramp window
during the SS1 function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
Code
(hex)
Name
Cause
What to do
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...