512 Maintenance
Drive control board boot
If you reboot the drive control board (for example, by cycling the power or with
parameter
96.08 Control board boot
(in DCS880 drives:
96.27 Control board boot
)),
the FSO module goes into the Fail-safe mode.
To exit the Fail-safe mode:
• switch the FSO module power off and then switch it back on, or
• reboot the FSO module with drive parameter
96.09 FSO reboot
(in DCS880
drives:
96.28 FSO reboot
), or
• click the
Reboot FSO
button in Drive composer pro.
Note
: The STO function must be completed before you can reboot the FSO module
with parameter
96.09 FSO reboot
(in DCS880 drives:
96.28 FSO reboot
) or with the
Reboot FSO
button. See section
.
Updates
After any changes in the safety application or the safety system configuration, you
must perform the acceptance tests to verify that the safety functionality is maintained.
See chapter
.
Proof tests
Periodic proof testing of the safety system may be required in order to maintain the
claimed SIL / PL level of the system, to ensure that the safety integrity of a safety
system is maintained continuously and does not deteriorate over time.
If proof testing is required, it must be taken into consideration in the safety
calculations, maintenance manuals, user documentation, and it must be done
periodically.
In high demand mode of operation, the maximum proof test interval for the FSO
module is 20 years. In low demand mode of operation, the maximum proof test
interval for FSO is 20, 5 or 2 years. You must select the proof test interval according
to the application where the modules are used. See section
Proof testing of the FSO module can be done by following the instructions in section
Validation of safety functions
. A reboot of the FSO module is necessary
for the proof test.
Decommissioning
WARNING!
Obey the instructions in chapter
. If you ignore
them, injury or death, or damage to the equipment can occur.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...