PROFIsafe 243
13. Return to the PROFINET controller (CM579-PNIO) properties. On the
Assign I/O
Device Name
tab:
•
Click
Connect to PLC (Login)
and select the communication link used
between Automation Builder and the PLC.
•
Click
Scan
to find all PROFINET devices connected to the network.
•
In the
Configure station name
box, select the station name defined for the
module in step 10 (in this example, drive1), and click
Assign I/O Device
name
.
•
In the
IP address
and
Network mask
boxes, type the IP address and subnet
mask defined in step 11, and click
Assign IP configuration
.
14. Define the I/O module properties:
•
Select the I/O module
PPO_Type_4
.
•
On the
General
tab, configure the Stop Mode Action and Control-zero mode
functions, and define Fail safe values for the PLC output process data (PZDs).
•
Rename the I/O modules, for example, drive1_PPO4 and drive1_ABB_PS1.
•
On the
PNIO Module I/O Mapping
tab, type names for the variables that refer
to the drive's signals in the PLC program. (See section
on page
.)
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...