206 PROFIsafe
Unsig
ned16
(used
as
bits)
5
0
SF_end_ack_req
Safety function ending acknowledgement
requested = 1,
no acknowledgement requested = 0.
Acknowledgement can be done via PROFIsafe.
Note:
These values are indicative only and shall
not be used for safety-related decisions about
safety function states (there are other ways to
safely determine the state of a function, for
example, using SS1 to check octet 0 bit 4 and
then octet 5 bit 4: if safe state, then SS1 is
completed).
1
SF_end_ack_req_lo
cal
Local safety function ending acknowledgement
requested = 1, no acknowledgement requested =
0.
Acknowledgement can only be done locally via
the FSO I/O if SF_end_ack_req is 0.
Note:
These values are indicative only and shall
not be used for safety-related decisions about
safety function states (there are other ways to
safely determine the state of a function, for
example, using SS1 to check octet 0 bit 4 and
then octet 5 bit 4: if safe state, then SS1 is
completed).
2
STO_control_active
The drive STO circuit is open.
Note
: The motor may still be rotating.
3
Speed_value_valid
Is the speed value valid (= 1) or not (= 0).
The speed value is defined in octets 6 and 7.
Note:
Octet 2 bit 0 indicates the speed source
and octet 5 bit 3 indicates the validity of the
indicated speed source.
4
FSO_state
Safe state = 1
Operational state = 0
5
FSO_mode.0
6
FSO_mode.1
7
Modulating
The drive is modulating = 1
It is not known if the drive is modulating or not = 0
WARNING!
The only safe way to make
sure that a drive is
not
modulating is to
activate drive STO. Drive STO can be
activated, eg, with FSO STO or POUS
function.
Type
Octet Bit Name
Description
FSO operating
mode
FSO_mode.1 FSO_mode.0
Start-up
0
0
Running
0
1
Fail-safe
1
0
Configuration
1
1
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...