64 Safety functions
You can configure one or two safety functions in the same cascaded system
(Cascade A and Cascade B). If the whole cascaded system must trip after reaching a
trip limit of any safety function, or with a safety fieldbus failure, you must cascade the
SSE function.
If an FSO module activates the STO function (after a limit hit, an STO request from
the I/O or the safety fieldbus, or after an internal fault), also the cascaded SSE output
is triggered.
Note
: When several drives are linked together in a master/follower system and the
follower drive is in the torque control mode, stopping functions with a deceleration
ramp (SSE with emergency ramp and SS1) will turn the follower drive to the speed
control mode. For more information on the master/follower functionality in the drive,
see the firmware manual.
Mute time feature
WARNING!
The mute time increases the response time of the safety system.
This must be considered in the design of the safety system.
Mute time feature with the safe speed estimation
When there are spurious transients in safe speed estimate, you can suspend speed
monitoring with mute time to prevent unnecessary trips in the safety system. The
transient mute time can be set to cover the transient situation with the parameter
. This transient mute time covers limit hits,
monitoring start, and zero speed limits.
It is also possible to use function-specific mute times for limit hit situations in SLSx,
SMS, and variable SLS functions with the safe speed estimate (starting from FSO
rev. J). Mute times for each of these functions can be set independently. In addition,
they can be set longer than the transient mute time
By default, these function-specific mute times are disabled, and the value set to
parameter
is used in limit hit situations instead.
Function-specific mute times for limit hit situations of the SLSx and variable SLS
functions can be enabled with the parameter
After the SLSx specific mute times have been enabled, the following mute time
parameters are used in limit hit situations.
•
•
•
•
•
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...