![ABB FSO-21 User Manual Download Page 407](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728407.webp)
Parameters 407
FSOGEN.38 Enable SLSx mute
times
Enables SLS-specific mute times which are
used in SLS limit hit situations.
These mute times can be set with
parameters
. These parameters
are effective only with the safe speed
estimate.
When this parameter is disabled,
is used in limit hit situations.
Disabled
Disabled
Deactivates SLSx mute times
Enabled
Activates SLSx mute times
FSOGEN.39 Enable SMS mute
time
Enables SMS-specific mute time, which is
used in limit hit situations and can be set
with parameter
. This parameter is
effective only with the safe speed estimate.
When this parameter is disabled,
is used in limit hit situations.
Disabled
Disabled
Deactivates SMS mute time
Enabled
Activates SMS mute time
FSOGEN.41 Power-up
acknowledgement
Sets the power-up acknowledgement
method.
Note
: If a safety function request is active
when the FSO module is rebooted, the
request must be removed before the power-
up acknowledgement is accepted.
Manual
The FSO module reads an external
acknowledgement signal through the digital
input defined by parameter
.
Automatic
The FSO module generates the
acknowledgement signal automatically after
the power-up.
Safebus
The FSO module expects an external
acknowledgement signal from the safety
fieldbus
after the power-up.
Manual_Safebus
The FSO module expects an external
acknowledgement signal either from a digital
input or from the safety fieldbus
after the
power-up.
FSOGEN.42 Acknowledgement
button input
Sets the digital input that is connected to the
button for acknowledgement operations.
None
No input connected
DI X113:1
Single input X113:1
DI X113:2
Single input X113:2
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...