PROFIsafe 229
Configuration
Configuring the FB module
You can use either the drive control panel or the Drive composer pro PC tool to
modify the settings of the FB module.
Note
: This section describes only the most important configuration steps. For more
detailed information, see FPNO-21 PROFINET fieldbus adapter module user’s
manual (3AXD50000158614 [English]),
FENA-01/-11/-21 Ethernet adapter module
user’s manual
(3AUA0000093568 [English]) and the drive firmware manual.
Note:
Example values in the table below are chosen based on the upcoming example
project.
Parameters for the PROFINET communication
1. Depending on the drive, you can configure the FB module as fieldbus channel A
or B. Enable the communication between the drive and the FB module for the
option slot where the FB module is installed in (parameter
50.01 FBA A enable
or
50.31 FBA B enable
).
2. Set the FB module parameters that correspond to the selected fieldbus channel.
Parameter groups 51, 52 and 53 include the settings for FBA A and groups 54, 55
and 56 for FBA B.
Groups 52, 53, 55 and 56 configure the contents of the normal PROFINET cyclic
communication by mapping the words in the PROFINET frame to the desired
drive parameters.
Groups 51 and 54 configure the PROFINET connection.
Index
Name/Value
Description
Example
value
50.01
FBA A enable
Enables/disables communication between the
drive and fieldbus adapter A and specifies the slot
the adapter is installed into.
1
Option slot 1
Communication between drive and fieldbus
adapter A enabled. The adapter is in slot 1.
50.31
FBA B enable
Enables/disables communication between the
drive and fieldbus adapter B, and specifies the
slot the adapter is installed into.
0
Disable
Communication between drive and fieldbus
adapter B disabled.
51/54.01
FBA A/B type
Shows the type of the connected fieldbus adapter
module A/B.
This parameter is read-only.
Ethernet
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...