Parameters 415
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
SBC.22 SBC feedback
action
Sets the action that the FSO module takes
when there is a problem with the SBC
feedback.
STO
The FSO module goes into the Fail-safe
mode and activates the drive STO function.
No STO
The FSO module sends a warning to the
drive.
SBC.23 SBC test OK signal Sets the digital output that indicates the
status of the SBC test OK signal. Active
when the SBC feedback indicates that the
SBC works correctly.
Note
: The feedback delay is 800 ms.
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7
Single output X113:7
DO X113:8
Single output X113:8
DO X113:9
Single output X113:9
DO X114:7
Single output X114:7
DO X114:8
Single output X114:8
DO X114:9
Single output X114:9
POUS
Parameters for the POUS function
POUS.01 POUS activity and
version
Activates or deactivates the POUS function
and shows the version of the POUS
function.
Disabled
Deactivates the POUS function.
Version 1
Activates version 1 of the POUS function.
POUS.02 POUS
acknowledgement
Sets the POUS acknowledgement method.
Manual
The FSO module reads the POUS
acknowledgement signal through the digital
input defined by parameter
. The FSO
module accepts the acknowledgement after
the POUS request has been removed.
Automatic
The FSO module generates the POUS
acknowledgement signal automatically after
the POUS request has been removed.
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...