Table 169: Channel configuration
Internal value
Operating modes of the analog outputs, individually configu-
rable
0 (default)
Not used
128
-10 V...+10 V
129
0 mA...20 mA
130
4 mA...20 mA
Table 170: Channel monitoring
Internal value
Check channel
0
Plausib(ility), cut wire, short circuit
3
None
Table 171: Substitute value
Intended behavior of output
channel when the control
system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF
Off
0
Last value infinite
Last value
0
Last value for 5 s and then
turn off
Last value 5 sec
0
Last value for 10 s and then
turn off
Last value 10 sec
0
Substitute value infinite
Substitute value
Depending on configuration
Substitute value for 5 s and
then turn off
Substitute value 5 sec
Depending on configuration
Substitute value for 10 s and
then turn off
Substitute value 10 sec
Depending on configuration
Group parameters for the digital part
Name
Value
Internal value
Internal value,
type
Default
Input delay
0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE
0.1 ms
0x00
Detect short cir-
cuit at outputs
Off
On
0
1
BYTE
On
0x01
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
820