2
1
UPx (+24 V)
ZPx (0 V)
Fig. 153: Digital input/output (circuit diagram)
1
Digital input/output
2
For demagnetization when inductive loads are turned off
Technical data of the fast counter
Parameter
Value
Used inputs
Terminal 2.0 (DI8),Terminal 2.1 (DI9)
Used outputs
Terminal 3.0 (DO8)
Counting frequency
Depending on operation mode:
Mode 1- 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Detailed description
See
1.7.4.2.10
Ordering data
Ordering No.
Scope of delivery
Product life cycle phase *)
1SAP 222 200
R0001
CI522-MODTCP, Modbus TCP com-
munication interface module, 8 DC,
8 DI and 8 DO
Active
1SAP 422 200
R0001
CI522-MODTCP-XC, Modbus TCP
communication interface module,
8 DC, 8 DI and 8 DO, XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.7.5 PROFINET
1.7.5.1
Comparison of the CI5xx-PNIO modules
The PROFINET IO devices combine the advantages of decentralized I/O modules with the
reaction time of AC500 mounted central I/O modules. The devices for PROFINET provide the
extension -PNIO in the device name.
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
794