Table 26: Assignment of the terminals:
Terminal
Signal
Description
1
NC
Not connected
2
O0
Output signal O0
3
O1
Output signal O1
4
O2
Output signal O2
5
O3
Output signal O3
6
UP
Process supply voltage UP +24 V DC
7
ZP
Process supply voltage ZP 0 V DC
The internal power supply voltage for the module's circuitry is carried out via the connection to
CPU. Thus, the current consumption from 24 V DC power supply at the terminals L+ and M of
the CPU module increases by 10 mA per TA5105-4DOT.
The external power supply connection is carried out via the UP (+24 V DC) and ZP (0 V DC)
terminals.
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
–
connect or disconnect any signal or terminal block
–
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.