Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Process voltage
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for
0 V (ZP)
Rated value
24 V DC
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse on UP
10 A fast
Galvanic isolation
Yes, per module
Current consumption
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
Ca. 2 mA
Current consumption from UP at normal oper-
ation
0.15 A + output loads
Inrush current from UP (at power up)
0.040 A
2
s
Max. length of analog cables, conductor cross sec-
tion > 0.14 mm
2
100 m
Weight
300 g
Mounting position
Horizontal or vertical with derating
(output load reduced to 50 % at 40 °C
per group)
Cooling
The natural convection cooling must not
be hindered by cable ducts or other
parts in the switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
498