Internal data exchange
Digital inputs (bytes)
0
Digital outputs (bytes)
1
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software, versions
≥
1.2.3.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...7
Name
Value
Internal
value
Internal
value,
type
Default
Min.
Max.
Max.
Module ID Internal
1105
1
)
WORD
1105
0x0451
0
65535
0x0Y01
Ignore
module
2
)
No
Yes
0
1
BYTE
No
0x00
not for
FBP
Parameter
length
Internal
6
BYTE
6-CPU
6-FBP
0
6
0x0Y02
Check
supply
Off
on
0
1
BYTE
On
0x01
0
1
0x0Y03
Reserve
0...255
0...0xff
BYTE
On
0x01
0
1
0x0Y04
Behaviour
of outputs
at com-
munica-
tion errors
Off
Last value
Substitute
value
0
1+(n*5)
2+(n*5),
n
£
2
BYTE
Off
0x00
0
2
0x0Y05
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
323