Fig. 50: 16 analog outputs in two groups
Chapter 1.6.2.2.4.2 “Functionality” on page 486
CAUTION!
By installing equipotential bonding conductors between the different parts of the
system, it must be ensured that the potential difference between ZP and AGND
never can exceed 1 V.
CAUTION!
The process supply voltage must be included in the grounding concept (e. g.
grounding of the negative pole).
The modules provide several diagnosis functions
Chapter 1.6.2.2.4.7 “Diagnosis”
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
489