1.7.2.2.5 Addressing
A detailed description concerning addressing can be found in the documentation of ABB Control
Builder Plus Software.
The CANopen communication interface module reads the position of the rotary
switches only during power-up, i. e. changes of the switch position during oper-
ation will have no effect until the next module initialization.
The range of permitted CANopen slave addresses is 1 to 127. Setting a higher
address (> 128) does not lead to an error response, but results in a special
mode (DS401). In this special mode, the device creates the node address by
subtracting the value 128 from the address switch's value.
1.7.2.2.6 I/O configuration
The CI582-CN CANopen bus configuration is handled by CANopen master with the exception of
the slave node ID (via rotary switches) and the transmision rate (automatic detection).
The digital I/O channels and the fast counter are configured via software.
1.7.2.2.7 Parameterization
Parameters of the module
Name
Value
Internal value
Internal value,
type
Default
Module ID
1
)
Internal
0x1C84
WORD
0x1C84
Parameter length Internal
54
BYTE
54
Error LED / Fail-
safe function
(table error LED /
Failsafe function
On
0
BYTE
0
Off by E4
1
Off by E3
2
On + failsafe
16
Off by E4 + fail-
safe
17
Off by E3 + fail-
safe
18
Reserved
0
0
ARRAY of 24
BYTES
Check supply
(UP and UP3)
On
0
BYTE
Off
1
1
Fast counter
0
0
BYTE
0
:
:
10
2
)
10
1
) With a faulty ID, the module reports a "parameter error" and does not perform cyclic process
data transmission
2
) For a description of the counter operating modes, please refer to the fast counter section
Chapter 1.6.1.2.9 “Fast counter” on page 349
Device specifications
Communication interface modules (S500) > CANopen
2022/01/31
3ADR010278, 3, en_US
640