Table 154: States of the 29 process LEDs
LED
Color
OFF
ON
Flashing
DC0 to DC7
Yellow
Input/Output is
OFF
Input/Output is
ON
--
DI8 to DI15
Yellow
Input is OFF
Input is ON (the
input voltage is
even displayed if
the supply
voltage is OFF)
--
DO8 to DO15
Yellow
Output is OFF
Output is ON
--
UP
Green
Process supply
voltage missing
Process supply
voltage OK and
initialization fin-
ished
--
UP3
Green
Process supply
voltage missing
Process supply
voltage OK
--
CH-ERR1 to CH-
ERR3
Red
No error or
process supply
voltage missing
Internal error
Error on one
channel of the
corresponding
group
1.7.3.2.11
Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Bus connection
2 x RJ45
Technology
Hilscher NETX 100
Transfer rate
10/100 Mbit/s (full-duplex)
Transfer method
According to Ethernet II, IEEE 802.3
Ethernet
100 base-TX, internal switch, 2x RJ45 socket
Expandability (S500 I/O modules)
Up to 10 S500 I/O modules (Index C0 and
above), not available (Index below C0)
Indicators
5 LEDs for state indication
Adjusting elements
2 rotary switches (used for future topology
extensions)
Quantity of input/output data
CI512-ETHCAT: 10 bytes input and 14 bytes
output
CI511-ETHCAT: 18 bytes input and 18 bytes
output
Limit of data for input and output
144 byte
Device specifications
Communication interface modules (S500) > EtherCAT
2022/01/31
3ADR010278, 3, en_US
723