NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Technical data of the analog outputs
Parameter
Value
Number of channels per module
2 configurable voltage or current outputs
Distribution of channels into groups
1 (2 channels per group)
Connection of the signals O0U- and O1U+
Terminals 13 and 15
Connection of the signals O0I+ and O1I+
Terminals 14 and 16
Output type
Bipolar with voltage, unipolar with current
Resolution
12 bits or 11 bits plus sign
Conversion error of the analog values
caused by non-linearity, adjustment error
at factory and resolution within the normal
range
Typ.
±
0.5 % of full scale
at 25 °C
Max.
±
2 % of full scale
at 0 °C...+60 °C or EMC disturbances
Indication of the output signals
No
Output Resistance (load) as current output
0
W
...500
W
Output load ability as voltage output
±
2 mA max.
Output data length
4 bytes
Relationship between output signal and hex
code
Chapter 1.6.2.1.4.8 “Output ranges”
Unused outputs
Must not be connected and must be configured
as "unused"
Overvoltage protection
Yes, up to 30 V DC
Max. cable length (conductor cross section
> 0.14 mm
²
)
Unshielded wire
10 m
Shielded wire
100 m
Ordering data
Part no.
Description
Product life cycle phase *)
1TNE 968 902 R1201 AO561, analog output module, 2 AO,
U/I
Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US