Without the fast counter
With the fast counter (only
with AC500)
Counter input data (words)
0
4
Counter output data (words)
0
8
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version
Configuration
Firmware version > V2.0.0
The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
No.
Name
Value
Internal
value
Internal
value,
type
Default
Min.
Max.
EDS
Slot/
Index
1
Module
ID
Internal
1000
1
)
Word
1000
0x03E8
0
65535
0x0Y01
2
Ignore
module
2
)
No
Yes
0
1
Byte
No
0x00
Not for
FBP
3
Param-
eter
length
Internal
3-CPU
2-FBP
Byte
3
2
0
255
0x0Y02
4
Check
supply
Off
On
0
1
Byte
On
0x01
0
1
0x0Y03
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
306