Internal value
Operating modes of the analog inputs, individually configurable
19
3-wire Ni1000 -50 °C...+150 °C *)
*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent
analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels
are configured in the desired operating mode. The lower address must be the even address
(channel 0). The next higher address must be the odd address (channel 1). The converted
analog value is available at the higher address (channel 1).
Table 168: Channel monitoring
Internal Value
Check Channel
0 (default)
Plausib(ility), cut wire, short circuit
3
Not used
Channel parameters for the analog outputs (2x)
Name
Value
Internal value
Internal value,
type
Default
Output 0,
Channel configu-
ration
Table Operating
modes of the
analog outputs
Table Operating
modes of the
BYTE
0
Output 0, Check
channel
Table Channel
monitoring
Table Channel
BYTE
0
Output 0, Substi-
tute value
Table Substitute
Table Substitute
value
WORD
0
Output 1,
Channel configu-
ration
Table Operating
modes of the
analog outputs
Table Operating
modes of the
BYTE
0
Output 1, Check
channel
Table Channel
monitoring
Table Channel
BYTE
0
Output 1, Substi-
tute value
Table Substitute
Table Substitute
value
WORD
0
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
819