NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
–
Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
–
Never connect any voltages or signals to reserved terminals (marked with
"NC"). Reserved terminals may carry internal voltages.
The following figure shows the connection of the option board for digital I/O extension
TA5105-4DOT:
NOTICE!
Risk of malfunctions in the plant!
Only if L+/M of the CPU is available and the outputs are already configured in
the AB program, the outputs will switch on as soon as the UP/ZP is available.
This must be considered in the application planning.
NOTICE!
Risk of damaging the I/O module!
The outputs are not protected against short circuits and overload.
–
Never short-circuit or overload the outputs.
–
Never connect the outputs to other voltages.
–
Use an external fuse for the outputs.
The module provides several diagnosis functions, see Diagnosis
.
The meaning of the LEDs is described in the section State LEDs
.
The module itself does not store configuration data. It receives its parameterization data from
the CPU module during power-up of the system.
Hence, replacing optional modules is possible without any re-parameterization via software.
The arrangement of the parameter data is performed with Automation Builder software.
I/O configura-
tion
Parameteriza-
tion
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US