The module itself does not store configuration data. It receives its parameterization data from
the CPU module during power-up of the system.
Hence, replacing optional modules is possible without any re-parameterization via software.
The arrangement of the parameter data is performed with Automation Builder software.
1.
In the device tree, double-click the desired option board.
2.
Select the
“TA51xx Parameters”
tab to edit the parameterization of the desired option
board.
1.
In the device tree, double-click the desired option board.
2.
Select the
“Diagnosis”
tab to view the diagnosis messages of the desired option board.
Table 24: Diagnosis messages
Device
Severity
Error
code
Description
Error Message
Remedy
TA5101-4DI
11
1
Wrong or no board
plugged
Replace with correct func-
tional board
TA5101-4DI
11
2
Board defective
Replace with correct func-
tional board
TA5101-4DI
11
3
Failed to set direction
Replace with correct func-
tional board
TA5101-4DI
11
4
Parameter wrong
Verify setting of parameter
“Run on config fault”
LED
State
Color
LED = OFF
LED = ON
Inputs I0...I3
Digital input
Yellow
Input is OFF
Input is ON
I/O configura-
tion
Parameteriza-
tion
Diagnosis
State LEDs
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US