Data of I/Os
PM5012-x-ETH
PM5032-x-ETH
PM5052-x-ETH
PM5072-T-2ETH
Type of digital
outputs
PM5012-T-ETH:
Transistor
PM5032-T-ETH:
Transistor
PM5052-T-ETH:
Transistor
PM5072-T-2ETH:
Transistor
PM5012-R-ETH:
Relay
PM5032-R-ETH:
Relay
PM5052-R-ETH:
Relay
-
Channels for
transistor version
4
(5 kHz standard
and PWM)
8
(incl. 4 fast outputs for standard or 4 PWM/2 PTO
(100 kHz/200 kHz), 4 standard outputs (5 kHz))
Channels digital
input/output con-
figurable
(valid for both
PLC version
relais or tran-
sistor)
-
2
Relay version:
The DC channels can be used as
1 PTO/2 PWM (100 kHz) or standard
digital inputs/outputs
Transistor version:
The DC channels can only be used
as standard digital inputs/outputs
2
Transistor ver-
sion:
The DC channels
can only be used
as standard dig-
ital inputs/outputs
Rated voltage
transistor
24 V DC
Nominal current
per transistor
channel
0.5 A resistive
Channels for
relay version
4
6
-
Rated voltage
relay
100 V AC...240 V AC
or
24 V DC
-
Nominal current
per relay channel
2 A resistive
-
Analog inputs
Optional
Analog outputs
Optional
Number of option
board slots
1
2
3
3
Usage of option
board
Each slot can be used for all type of existing option boards, same option
board for serial interface or digital/analog I/O extension can be used on
several slot per CPU.
Note: RTC option board is only for PM5012 possible.
KNX address
switch
No
TA5130-KNXPB
only on 1 slot
Real-time clock
(RTC)
TA5131-RTC
No
Serial interface
TA5141-RS232I, TA5142-RS485/TA5142-RS485I
Digital in/out
channels
TA5101-4DI, TA5105-4DOT, TA5110-2DI2DOT
Analog in/out
channels
TA5120-2AI-UI, TA5122-2AI-TC, TA5123-2AI-RTD, TA5126-2AO-UI
Max. number of
I/O modules on
I/O bus
0
10
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
48