The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Process supply voltage
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24
V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V
DC)
Protection against reverse voltage
yes
Rated protection fuse at UP
10 A fast
Rated value
24 V DC
Max. ripple
5 %
Current consumption
From UP
0.07 A + max. 0.5 A per output
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
ca. 2 mA
Inrush current from UP (at power-up)
0.04 A
2
s
Galvanic isolation
Yes, per module
Max. power dissipation within the module
6 W (outputs unloaded)
Weight (without terminal unit)
ca. 125 g
Mounting position
Horizontal mounting or vertical with
derating (output load reduced to 50 % at
40 °C)
Cooling
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US