Table 94: Channel monitoring
Internal
value
Monitoring
0
Plausibility, open-circuit (cut wire) and short circuit (default)
3
No monitoring
Table 95: Line frequency suppression
Internal
value
Line frequency suppression
0
50 Hz
1
60 Hz
2
No line frequency suppression
Table 96: Compensation channel
Internal
value
Compensation channel
0
Internal compensation (default)
1
Channel 0 (possible with channels 1, 2, 3)
2
Channel 1 (possible with channels 0, 2, 3)
3
Channel 2 (possible with channels 0, 1, 3)
4
Channel 3 (possible with channels 0, 1, 2)
5
Channel 4 (possible with channels 5, 6, 7)
6
Channel 5 (possible with channels 4, 6, 7)
7
Channel 6 (possible with channels 4, 5, 7)
8
Channel 7 (possible with channels 4, 5, 6)
9
External with temperature value
Diagnosis
E1...E4
d1
d2
d3
d4
Identifier
000...063
AC500
display
<− Display in
Class
Comp
Dev
Mod
Ch
Err
PS501
PLC
browser
Byte 6
Bit 6...7
-
Byte 3
Byte 4
Byte 5
Byte 6
Bit 0...5
FBP diag-
nosis
block
Class
Interface
Device
Module
Channel
Error
identifier
Error message
Remedy
1
)
2
)
3
)
4
)
Module error
3
14
1...10
31
31
19
Checksum error in the
I/O module
Replace
I/O module
11 / 12
ADR
1...10
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
475