The system data of AC500-eCo V3 apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Process supply voltage UP
Connections
Terminal 6 for UP (+24 V DC) and ter-
minal 7 for ZP (0 V DC)
Rated value
24 V DC
Current consumption via UP terminal
5 mA + max. 0.5 A per output
Max. ripple
5 %
Inrush current
0.000002 A
²
s
Protection against reversed voltage
Yes
Rated protection fuse for UP
On request
Current consumption from 24 V DC power supply
at the L+/M terminals of the CPU
Ca. 10 mA
Galvanic isolation
Yes, between the input group and the
output group and the rest of the module
Isolated groups
2 groups (1 group for 2 input channels, 1
group for 2 output channels)
Surge-voltage (max.)
35 V DC for 0.5 s
Max. power dissipation within the module
0.7 W
Weight
15 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
Table 31: Technical data of the digital inputs
Parameter
Value
Number of channels per module
2
Distribution of the channels into groups
1 group for 2 channels
Connections of the channels I0 to I1
Terminals 2 to 3
Reference potential for the channels I0 to I1
Terminal 1
Indication of the input signals
1 yellow LED per channel; the
LED is ON when the input signal
is high (signal 1)
Monitoring point of input indicator
LED
It is not part of input circuit (its
controlled by processor side, not
process side)
Input type according to EN 61131-2
Type 1 source
Type 1 sink
Input signal range
-24 V DC
+24 V DC
Signal 0
-5 V...+3 V
-3 V...+5 V
Technical data
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
69