State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED
State
Color
LED = OFF
LED = ON
LED flashes
Inputs/
outputs
C0...C23
Digital input
or digital
output
Yellow Input/output
= OFF
Input/output =
ON
1
)
--
UP
Process
supply
voltage
24 V DC via
terminal
Green Process
supply
voltage is
missing
Process
supply voltage
OK
--
CH-ERR1
Channel
error, error
messages in
groups (dig-
ital inputs/
outputs com-
bined into the
groups 1, 2,
3, 4)
Red
No error or
process
supply
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
corresponding
group (e.g.
short circuit at
an output)
CH-ERR2
Red
CH-ERR3
Red
CH-ERR4
Red
CH-ERR
2
) Module error Red
--
Internal error
--
1
) Indication LED is ON even if an input signal is applied to the channel and
the supply voltage is off. In this case the module is not operating and does not
generate an input signal.
2
) All of the LEDs CH-ERR1 to CH-ERR4 light up together
Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Process supply voltage UP
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as
well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value
24 V DC
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse on UP
10 A fast
Galvanic isolation
Yes, per module
Current consumption
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
286