The index of the module is in the right corner of the label.
NOTICE!
Risk of damage to I/O modules!
Modules with index below F0 can be damaged when inserted or removed from
the terminal unit in a powered system.
NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Device
Min. required device index for I/O module as of
FW Version 3.0.14
AC522(-XC)
F0
AI523 (-XC)
D2
AI531
D4
AI531-XC
D2
AI561
B2
AI562
B2
AI563
B3
AO523 (-XC)
D2
AO561
B2
AX521 (-XC)
D2
AX522 (-XC)
D2
AX561
B2
CD522 (-XC)
D1
DA501 (-XC)
D2
DA502 (-XC)
F0
DC522 (-XC)
D2
DC523 (-XC)
D2
DC532 (-XC)
D2
DC561
B2
DC562
A2
DI524 (-XC)
D2
DI561
B2
DI562
B2
DI571
B2
Device specifications
Terminal units (AC500 standard) > TU515, TU516, TU541 and TU542 for I/O modules
2022/01/31
3ADR010278, 3, en_US