Range
Pt100 / Pt1000
-50 ... +400 °C
Ni1000 / Ni100
-50 ... +150 °C
Digital value
Decimal
Hex.
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
Normal range
400.0 °C
:
:
:
:
0.1 °C
150.0 °C
:
:
0.1 °C
4000
2000
1500
700
:
1
0FA0
07D0
05DC
02BC
:
1
0,0 °C
0.0 °C
0
0000
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-1
:
-500
-2000
FFFF
:
FE0C
F830
Measured value
too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow
< -60.0 °C
< -60.0 °C
-32768
8000
Resistances
Range
Resistance 0 ...
150
W
Resistance 0 ...
300
W
Digital value
Decimal
Hex.
Overflow
>176.383
>352.767
32767
7FFF
Measured value
too high
176.383
150.005
352.767
300.011
32511
27649
7EFF
6C01
Normal range
150.000
:
0.005
300.000
:
0.011
27648
:
1
6C00
:
0001
0
0
0
0000
Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
368