Terminal
Signal
Description
1
C0...7
Input common for signals I0 to I7
2
I0
Input signal I0
3
I1
Input signal I1
4
I2
Input signal I2
5
I3
Input signal I3
6
I4
Input signal I4
7
I5
Input signal I5
8
I6
Input signal I6
9
I7
Input signal I7
10
C8...15
Input common for signals I8 to I15
11
I8
Input signal I8
12
I9
Input signal I9
13
I10
Input signal I10
14
I11
Input signal I11
15
I12
Input signal I12
16
I13
Input signal I13
17
I14
Input signal I14
18
I15
Input signal I15
19
---
Reserved
20
---
Reserved
The internal power supply voltage for the module's circuitry is carried out via the I/O bus
(provided by a communication interface module or a CPU). Thus, the current consumption from
24 V DC power supply at the terminals L+/UP and M/ZP of the CPU/communication interface
module increases by 10 mA per DI562.
An external power supply connection is not needed.
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
–
connect or disconnect any signal or terminal block
–
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US