LED
Color
State
Description
Off
No Ethernet connection
PNIO2 LED "RX/TX" Yellow
On
---
Blinking
PROFINET device sends/receives
frames
Off
---
1.4.5.1.5 Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Protocol
PROFINET IO RT
Bus connection
2 RJ45 (PNIO1 and PNIO2), with integrated 2-
port switch
Switch
Integrated
Technology
Hilscher NETX 100
Transfer rate
100 Mbit/s (full-duplex)
Transfer method
According to Ethernet II, IEEE 802.3
Ethernet
100 base-TX, internal switch, 2x RJ45 socket
Bus length (segment length max.)
100 m
Indicators
5 LEDs
Usable terminal bases
All TB5xx
“TB56xx for AC500 V3 products” on page 4
Supported alarm types
Process alarm, diagnostic alarm, return of Sub-
Module, plug alarm, pull alarm
Alarm processing
Requires handling in application program
Current consumption from 24 V DC power
supply at the terminal base of the CPU
Typ. 85 mA
Internal supply
Via the communication module interface of the
terminal base
Weight
Ca. 170 g
Device specifications
Communication modules (AC500 standard) > PROFINET