Range
-50 ...
+50 mV
-500 ...
+500
mV
-1 ... +1
V
-5 ... +5
V
-10 ...
+10 V
Commo
n Mode
Voltage
Digital value
Decimal
Hex.
Meas-
ured
value
too low
-50.0018
:
-58.7945
-500.018
1
:
-587.944
9
-1.00004
:
-1.17589
-5.0002
:
-5.8794
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Under-
flow
<
-58.7945
<
-587.944
9
<
-1.17589
<
-5.8794
<
-11.7589
<
-20.0000
-32768
8000
Unipolar voltage input range, measuring bridge, digital input
Range
0 ... +5 V
0 ... +10 V Digital
input
Digital value
Decimal
Hex.
Measured
value too
high
5.8794
:
5.0002
11.7589
:
10.0004
32511
:
27649
7EFF
:
6C01
Normal
range
5.0000
:
0.0002
10.0000
:
0.0004
ON
27648
:
1
6C00
:
0001
0.0000
0.0000
OFF
0
0000
Measured
value too
low
-0.0002
:
-0.8794
-0.0004
:
-1.1759
-1
:
-4864
FFFF
:
ED00
Underflow
< -0.8794
< -1.1759
-32768
8000
Current input ranges
Range
-20 ... +20
mA
0 ... +20 mA 4 ... 20 mA
Digital value
Decimal
Hex.
Overflow
> 23.5178
> 23.5178
> 22.8142
32767
7FFF
Measured
value too
high
23.5178
:
20.0007
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
:
6C01
Normal
range
20.0000
:
0.0007
20.0000
:
0.0007
20.0000
:
4.0006
27648
:
1
6C00
:
0001
0.0000
0.0000
4.0000
0
0000
-0.0007
:
-20.0000
-1
:
-27648
FFFF
:
9400
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
479