Custom V/F Curve Setting:
A custom curve selection allows users to set parameters 01-02 ~ 01-13 whereas a predefined curve selection
does not.
Output Voltage
(V)
( 01 - 03 ) Vmax
( 01- 05 )
Vmid
1
( 01 -
07)
Vmid
2
( 01 -
09)
Vmin
Fmin
( 01- 08)
Fmid
2
( 01- 06)
Fmid
1
(01- 04)
Fbase
(01- 12)
Fmax
( 01- 02)
Output
Frequency
(Hz)
( 01 - 13) Vbase
Figure 4.3.12 Custom V/F curve
Output Voltage (V)
Vmax
Vmid2
Vmin
Fmid2
(01- 04)
Fbase
( 01 - 12
Fmax
( 01 - 02 )
Vmid1
Fmid1
( 01 - 06)
Fmin
(01- 08)
)
Figure 4.3.13 Torque boosting
When setting the frequency related parameters for a custom V/F curve values make sure that:
F
max
> F
base
> F
mid2
>
F
mid1
>F
min
(01-02) (01-12) (01-04) (01-06) (01-08)
The ‘SE03’ V/F curve tuning error is displayed when the frequency values are set incorrectly.
When 01-04 and 01-05 (or 01-18 and 01-19) are set to 0, the inverter ignores the set values of Fmin2 and Vmin2.
The voltage values for 01-02~01-09 become
irrelevant.
The value for maximum output voltage of the motor 1(01-03) and the value for base output voltage of the motor
(01-13) will depend on the initial setting of 13-08 which sets the value of voltage upon initialization.
When the control mode is changed parameter 00-00, 01-08 (F
min
) and 01-09 (V
min
) will automatically be changed
to the default setting of the selected control mode.