4-109
03-0X =06:
Forward jog run command, uses jog frequency parameter 00-18.
Note:
Jog command has a higher priority than other frequency reference commands.
Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms.
03-0X =07:
Reverse jog run command, uses jog frequency parameter 00-18.
03-0X =08:
UP frequency command
03-0X =09:
Down frequency command
Inverter can use the digital operator and external digital input (S1~S6) to increase or decrease output frequency
while motor is running. To use the external digital inputs are used to perform UP/DOWN, set 00-02=1, 00-05=4
and 03-0X=8 and 9, this function requires both UP and DOWN functions 08 and 09 to be programmed to two of
the digital input terminals.
UP/DOWN frequency command follows the standard acceleration and deceleration times
SE02 DI terminal error will be displayed when:
When only one UP or DOWN command is programmed for the digital inputs.
When DOWN command and Inhibit Acceleration/deceleration command are activate simultaneously.
When UP command and Inhibit Acceleration/deceleration command are active simultaneously.
For an example of UP/DOWN control wiring and operation, please refer to figure 4.3.19 and figure 4.3.20.
UP Command
(Terminal S5)
1
0
0
1
Down Command
(Terminal S6)
0
1
0
1
Operation
Accel
(UP)
Decel
(DWN)
Hold
Hold
Figure 4.3.19 UP/DOWN wiring and operation example
S1 Forward Run / Stop (03-00 = 0)
24VG
S5 Up Command (03-04=8)
S6 Down Command (03-04=9)