4-202
Unlocking the inverter with key code (password):
Unlock
▲
▼
or
READ/
ENTER
Password Entered Successfull
Password Entered Failed
▲
▼
or
READ/
ENTER
READ/
ENTER
DSP/
FUN
DSP/
FUN
13-08
Restore factory setting / Initialize
Range
【
1
】
: 2 wires initialization (50Hz) (220V/380V)
【
2
】
: 2 wires initialization (60Hz) (220V/380V)
【
3
】
: 2 wires initialization (50Hz) (230V/400V)
【
4
】
: 2 wires initialization (60Hz) (230V/460V)
【
5
】
: 2 wires initialization (50Hz) (220V/415V)
【
6
】
: 2 wires initialization (60Hz) (230V/400V)
【
7
】
: 2 wires initialization (50Hz) (220V/440V)
【
8
】
: 2 wires initialization (60Hz) (220V/440V)
【
1112
】
: PLC initialization (RESET)
Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down the modified
parameters before initializing the inverter. After initialization, the value of 13-08 will return to zero automatically
13-08=1: 2 Wire Initialization (220V/380V)
Multi-function digital input terminal S1 controls forward operation / stop command and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 380V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically be set to 50Hz.
13-08=2: 2 Wire initialization (220V/380V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 380V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.