8-4
8.4
Emergency Stop
Deceleration time 2 is used in combination with multi-function digital input function #14 (Emergency stop). When
rapid stop input is activated the inverter will decelerate to a stop using the Deceleration time 2 (00-17) and display
the [E.S.] condition on the keypad.
Note:
To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Example: Emergency Stop Switch set for input terminal S5 (03-04 = 14).
AO
24V
AI1
S6
S(+)
S(-)
AGND
10V
R2A
R2B
R1C
S1
S3
S5
AI2
R1A
SG
COM
S2
S4
SF1
R1B
Emergency
Stop Switch
Emergency Stop
Common
Control Terminals /
User Terminals
00-17
Deceleration Time 2
Range
0.1~6000.0 Sec