4-63
00-12
Upper Limit Frequency
Range
【
0.01~599.00
】
Hz
Set the maximum frequency reference. Maximum output frequency depends on motor selection.
Motor Maximum frequency parameter 01-02.
00-13
Lower Limit Frequency
Range
【
0.00~598.99
】
Hz
Set the maximum frequency reference is 100% of the 01-02 or 01-16.
The inverter will display the SE01 error when 00-12 value is set lower than value in parameter 00-13.
Frequency upper and lower limits are active for all frequency reference modes.
100%
00 - 12
00 - 13
100%
Output
Frequency
Frequency
Reference
Figure 4.3.6 Frequency reference upper and lower limits
00-14
Acceleration Time 1
Range
【
0.1~6000.0
】
Sec
00-15
Deceleration Time 1
Range
【
0.1~6000.0
】
Sec
00-16
Acceleration Time 2
Range
【
0.1~6000.0
】
Sec
00-17
Deceleration Time 2
Range
【
0.1~6000.0
】
Sec
Notes:
- Acceleration time is the time required to accelerate from 0 to 100% of maximum output frequency.
- Deceleration time is the time required to decelerate from 100 to 0% of maximum output frequency.
- Maximum frequency is set by parameter 01-02 or 01-16.
- If parameter 01-00=18, Maximum output frequency is set by parameter 01-02 or 01-16.
- If parameter 01-
00≠18, Maximum output frequency = 50.00 or 60.00 depending on initialization mode.