4-195
11-55
STOP Key Selection
Range
【
0
】
:
Stop key is disabled when the operation command is not set to operator control
【
1
】
:
Stop key is enabled when the operation command is not set to operator control
This function can be used to enable or disable the stop key on keypad display when 00-02 is set to 1 (external
terminal) or 00-02 is set to 3 (communication).
11-55= 0: Stop button disabled.
11-55= 1: Stop button enabled.
11-59
Gain of Preventing Oscillation
Range
【
0.00~2.50
】
This parameter is used to prevent motor oscillation (hunting prevention).
If oscillation (hunting) occurs under normal operation (normal duty mode), increase the setting value by 0.01
increments.
11-60
Upper Limit of Preventing Oscillation
Range
【
0~100
】
%
Motor oscillation (hunting) prevention upper limit.
11-61
Time Parameter of Preventing Oscillation
Range
【
0~100
】
Hunting prevention response delay time is the delay time used to prevent motor oscillation.
11-62
Selection of Preventing Oscillation
Range
【
0
】
: Mode 1
【
1
】
: Mode 2
【
2
】
: Mode 3
11-62=0:
Mode 1,
lower response to prevent oscillation.
11-62=1:
Mode 2,
medium response to prevent oscillation.
11-62=2:
Mode 3, fast response to preventing oscillation.
11-63
Strong Magnetic Selection
Range
【
0
】
: Disable
【
1
】
: Enable
11-63=0: No adjustment of the magnetizing current. The magnetizing current is the same at low and high speeds.
11-63=1: Magnetizing current is automatically increased at lower speed (increase in motor torque). Best used in
constant torque applications where increased starting toque is required.